BeneTerra’s BeneVap technology holds a mobile waste processing licence issued by the NSW EPA. This licence allows us to operate at any landfill site in NSW for up to 6 months of every year without the requirement to alter the site’s environmental licence. This is a great option for facilities that do not require a fulltime BeneVap to manage leachate volumes, allowing them to prepare their storage facilities for the wet season.
Our licence number is 21343.
As part of our licence conditions we report on the monitoring we undertake from BeneVap stack emissions.
Parameter | Result | Unit | Exceedance (yes/no) |
Sample dates | 20/02/2025 | dd/mm/yyyy | |
Average source temperature | 86 | °C | No |
Flue gas water vapour content | 54.4 | vol-% | No |
Carbon dioxide concentration | 9.7 | vol-% | No |
Oxygen concentration | 7.4 | vol-% | No |
Flue gas molecular weight – dry | 1.33 | kg/Nm3 | No |
Flue gas velocity | 3.26 | m/sec | No |
Oxides of nitrogen (as NO2) emission rate |
129 2.46 |
mg/Nm3 g/min |
No |
Carbon monoxide emission rate |
36 0.39 |
mg/Nm3 g/min |
No |
We also maintain a Pollution Incident Repsonse Plan (PIRMP) which you can view here.